The transformers are built in accordance with IS 2026/IS 11171 and IEC 726 standards
The core is built of cold rolled oriented grain steel with low specific losses, insulated on both sides by a thin inorganic coating (Carlyte). The sheets composing the core are cut at 45 degrees C. Uniform pressing, stiffness and solidity of the columns assure a low noise level.
The high voltage windings are realized by disc/ Comb winding, depending on the feeding voltage and transformer power. The copper conductor is NOMEX/FIREGLASS insulated or class H enamel. Adequate axial channels between the layers of windings grant a uniform cooling. Insulation between high and low voltage and core is made by fibreglass cylinders. All the winding are dried in an oven and impregnated under vacuum by using class F/H insulating Varnishes/ Resin.
The low voltage windings are made of copper Strip/Foil (Above 1000 KVA). This modern technology assures an excellent resistance to electrodynamic stresses, much higher than the one obtained with traditional elix windings. The insulation between windings is obtained by using class F/H material.
Test:
All transformers are individually tested with routine test, according to standard IS 2026/ 11171 and IEC 726. Upon request the following type test can be carried out.
| Standard Applicable : | IS 2026, IS 11171, IEC 726 |
| TYPE : | Open / Enclosed |
| Temperature Class : | 155/140/120 °C |
| Insulation class : | H / F /B |
| Protection Class | IP-21/23/33/44 |
| Installation | Indoor / Outdoor |